Stack effect is the vertical movement of air through a building caused by the indoor-outdoor temperature difference. In winter, warm air rises and leaks out near the top while cold outdoor air is drawn in near the bottom. When the building is cooler than outdoors, the tendency reverses, though wind and mechanical systems also shape the actual flow.
In a multi-story commercial building, the pressure behind that airflow grows with height and temperature difference and acts on entrances, shafts, and air handlers. A system can be balanced to design and still misbehave when the weather changes.
Below: how stack effect works, how strong it gets in Texas, the symptoms, where it meets HVAC and life safety systems, and what TAB measures and corrects.
How Stack Effect Works in a Commercial Building
Warm air is less dense than cold air, so the pressure difference between a warm indoor column and a cold outdoor column grows with height and temperature gap. National Research Council Canada’s research on stack effect in buildings puts it simply: stack effect in a building “is the same as stack effect in a chimney.”
Infiltration is unintended outdoor air entering the building; exfiltration is indoor air leaving through leakage paths. Stack effect drives both at once, at different heights.
The Neutral Pressure Plane
In a simplified stack-only model, the neutral pressure plane is the level “where the inside and outside pressures are equal.” When the building is warmer than outdoors, outdoor air infiltrates below that level and indoor air exfiltrates above it.
Where that plane sits depends on the relative resistance to airflow of the building’s components. All else being equal, large openings low in the building pull the neutral plane down, and tighter lower floors push it up. In a commercial building, EAB’s examples of those lower openings are main entrances, loading docks and parking garage connections.
In a compartmented building, floors and shafts may not share one neutral level.
Shafts Carry Most of the Vertical Flow
Stairwells, elevator hoistways and service shafts that penetrate the floors give air its vertical paths. Stack effect in high-rise buildings moves most of its upward flow through those shafts. As floor separations get tighter, more of the stack pressure falls across floors and shaft walls and less across the exterior wall.
A system set up through air balancing delivers design airflows under test conditions; stack effect keeps pushing on it as outdoor temperature moves.
Normal and Reverse Stack Effect
- Normal stack effect (winter): the building is warmer than outdoors. Air moves up, entering near the bottom and leaving near the top.
- Reverse stack effect (summer): the building is cooled below outdoor temperature. The tendency flips: outdoor air enters near the top and cooled air leaves near the bottom.
Infiltration and exfiltration happen in both seasons, at opposite ends of the building. Wind and mechanical systems also shape the actual airflow at any opening.
Simplified example of stack effect in winter and summer. The neutral level shown is illustrative; wind, mechanical systems, and compartmentalization change the actual pressure profile.
How Strong Stack Effect Gets in a Texas Building
Total stack pressure scales with building height and the indoor-outdoor temperature difference. NRC Canada gives the relationship as:
ps = 0.52 × P × H × (1/To − 1/Ti)
ps = total stack pressure across the building height, in. w.c.
P = atmospheric pressure, psia
H = total building height, ft
To, Ti = outdoor and indoor absolute temperatures, degrees Rankine (degrees F + 459.67)
A negative result indicates reverse stack effect.
For scale, NRC’s 1968 digest gave the example of a 50-story building with an outdoor temperature of -25 degrees F, which has a total stack effect of about 2 in. of water.
Using NRC’s formula, EAB estimates the following for Texas conditions, assuming 13 ft floor to floor:
| Building and condition | Assumed temperatures | Theoretical total stack pressure across full height | Idealized magnitude at each end (mid-height neutral plane, negligible internal losses) |
|---|---|---|---|
| 10 stories (130 ft), North Texas winter morning | 20 F outside, 72 F inside | about 0.20 in. w.c. | about 0.10 in. w.c. |
| 10 stories (130 ft), Texas summer afternoon | 100 F outside, 75 F inside | about 0.08 in. w.c. (reverse) | about 0.04 in. w.c. |
| 20 stories (260 ft), North Texas winter morning | 20 F outside, 72 F inside | about 0.41 in. w.c. | about 0.20 in. w.c. |
| 20 stories (260 ft), Texas summer afternoon | 100 F outside, 75 F inside | about 0.17 in. w.c. (reverse) | about 0.08 in. w.c. |
Notes: P = 14.7 psia. Constant-temperature, stack-only estimates that exclude wind and mechanical pressurization. Summer values are negative under the formula’s sign convention; the table reports magnitudes and labels them reverse.
These estimates show why seasonal building stack effect belongs in a pressure assessment. They do not predict the differential across any particular door, shaft, or wall; internal separations and leakage distribution decide that, which is why it has to be measured.
These 10- and 20-story winter examples produce smaller total stack pressures than NRC’s 50-story benchmark. A cold North Texas morning still produces a measurable effect in a mid-rise or high-rise, and, all else being equal, a cold snap pushes it higher.
Reverse stack effect is relevant whenever the building is cooled below outdoor temperature. It is weaker in these examples because the summer temperature difference is smaller. Wind also adds to or offsets stack effect at any given moment.
Signs Stack Effect Is Disrupting Your HVAC
None of these proves stack effect alone. They are clues that justify measurement.
- Entrance doors that fight you. Doors that are hard to open, stand ajar or will not latch, with winter drafts and dust. NRC’s research describes lower-level inflow causing cold drafts that are “particularly troublesome near entrances.”
- Elevator doors that whistle, bind, or fail to close. A 2024 study of pressure differences on high-rise elevator doors found stack effect “may produce a significant pressure difference on the elevator doors,” and that the state of the first-floor lobby entrance can affect that difference under the conditions investigated. Noise or operating difficulty is a clue; performance is judged against project requirements.
- Floors that will not hold temperature or humidity. Uneven vertical airflow “causes a variation in the heating and humidification load from floor to floor,” according to NRC. Lower floors take the cold infiltration; upper floors lose conditioned air.
- Odors moving between floors. Shafts carry odors and contaminants from one level to another.
- Condensation risk at upper levels in winter. Warm, moist air exfiltrating through the upper envelope can condense under suitable moisture and temperature conditions.
- Pressure readings and complaints that track the weather. When they shift with outdoor temperature rather than with any system change, stack effect is a suspect.
Where Stack Effect Meets the HVAC System
Start with the airflow totals: verify outdoor air, exhaust, and relief against the design intent, then measure the resulting building and zone pressure relationships. A net outdoor-air surplus can support positive building pressurization but does not guarantee the intended pressure at every floor or internal boundary. Healthcare buildings also have intentional local pressure relationships, so the target is the approved design, not “positive everywhere.”
Pressurization Moves Stack Effect; It Does Not Remove It
Mechanical systems are sometimes designed “to provide an excess of supply air and thus to pressurize the building.” NRC’s follow-up digest shows that pressurization changes where stack effect pressures land; it does not eliminate the effect.
NRC notes that the additional outdoor air needed for pressurization carries a heating cost penalty. In hot, humid Texas conditions, that extra outdoor air also adds cooling and dehumidification load.
Relief Matters as Much as Supply
EAB’s case on a hospital bed tower where building relief was the missing piece shows how building pressure and relief affect pressurization systems, though it does not identify stack effect as a cause. On that 15-story tower, Durwood Lassiter III, TBE, reports design (plan) outdoor air of 108,425 CFM against plan exhaust of 81,335 CFM, “providing a differential of 27,090 CFM of positive ventilation.” Initial testing found hoistway pressure shortfalls. The coordinated resolution added relief at multiple levels, adjusted lobby door clearances, and finished with system tuning.
The opposite failure: fresh air intakes are shut down while exhaust keeps running, so the building makes up the difference through doors and other openings. EAB’s article on exhaust running without enough make-up air describes exhaust systems that “pull fresh air into the building through whatever paths they can,” often at doorways and windows.
Stack Effect and Life Safety Systems
NRC’s research called smoke moving up shafts “one of the major problems in providing for fire safety in high buildings.”
IBC Section 909.4.1 requires smoke control systems to be designed so the maximum probable normal or reverse stack effect will not adversely interfere with their capabilities, using altitude, elevation, weather history, and interior temperatures to determine it. Project requirements follow the locally adopted edition and amendments, as enforced by the authority having jurisdiction.
On the hospital bed tower, the required hoistway differential was +0.10 to +0.25 in. w.c. Initial readings were +0.015 to +0.055 in. w.c. for the service car hoistways and +0.045 to +0.145 in. w.c. for the passenger car hoistways, so the systems did not meet the requirement throughout.
Record outdoor and indoor temperatures during stair and hoistway pressurization testing so the results can be interpreted later. A mild-day test may not show how the system performs at weather extremes; that does not invalidate a test that meets the applicable acceptance requirements.
For the testing side, see EAB’s guide to passing a smoke control acceptance test and its pre-TAB smoke testing checklist for detention facilities.
How TAB Diagnoses and Corrects Stack Effect Problems
EAB’s Total System Balance work includes verifying the “performance of pressurization and smoke control systems” and, for hospitals and laboratories, helping “pinpoint problems with pressurization systems.” Recommended diagnostic practice:
- Verify outdoor air, exhaust, and relief against the design intent. Measure them under the same operating condition, and confirm the building has a working relief path.
- Measure building pressure relative to outdoors at several levels. Start near the bottom, middle, and top to see where pressure changes sign for the space or shaft being tested. Add points as needed; three readings do not locate a building-wide neutral plane.
- Measure across the doors and shafts that complain. Take readings at entrance vestibules, elevator lobbies, hoistways, and stair doors, using micromanometers and other air balancing tools for very low pressure differences. Keep building-to-outdoor readings separate from shaft-to-adjacent-space readings; they describe different pressure boundaries.
- Record the conditions. Log the pressure reference and location, indoor and outdoor temperatures, wind, door states, and HVAC mode, so wind, controls, or open doors are not mistaken for stack effect. Survey under heating and cooling conditions where practical; recording temperatures on one mild-day visit is not the same as checking both seasons.
- Trend building static pressure. Where the BAS has building static pressure points, verify sensor accuracy and the outdoor reference location, then use trend data across changing weather.
- Correct within the approved design. Rebalance outdoor air and exhaust, verify building static pressure sequences and setpoints, confirm relief dampers and fans operate, and document suspected leakage paths.
TAB identifies and documents pressure problems, makes authorized adjustments within approved design requirements, and verifies the result. Changes to shaft or fire and smoke assemblies, door clearances, required airflow, relief systems or smoke control sequences require coordination with the responsible design professionals, contractors and, where applicable, the authority having jurisdiction. TAB does not seal the envelope.
For an occupied building already showing these symptoms, existing-building commissioning can investigate the broader HVAC and controls interactions using retro-commissioning or recommissioning as appropriate to the building’s history.
How to Reduce Stack Effect in Commercial Buildings
Stack effect cannot be prevented while a building has height and an indoor-outdoor temperature difference. The goal is to reduce the airflow it drives and control where the pressure lands.
Entrances
NRC notes that vestibule and revolving door entrances are common practice in high buildings to reduce door-opening forces and air infiltration, and that a vestibule “divides the pressure difference across the entrance.” The 2024 Energies study found that combining revolving doors in place of swing doors, added partitions, and a locally strengthened envelope reduced internal pressure difference in the building studied; that is one building’s result, not a universal rule.
Compartmentalization
Tighten floor separations and shaft walls. Where the exterior enclosure of some floors cannot be made tight, NRC notes it may be necessary to add “vestibule entrances around elevators and stairwells.”
Air Sealing the Envelope and Interior Separations
Building envelope and interior leakage paths to seal in commercial construction include:
- Penetrations through exterior walls and roofs
- Openings around windows and doors
- Roof and wall joints
- Shaft walls and floor penetrations
Verifying Envelope Tightness
Where applicable, 2021 IECC Section C402.5.3 uses a building thermal envelope air leakage criterion of 0.40 cfm/ft² of envelope area at 75 Pa (0.3 in. w.c.). Testing provisions and exceptions depend on occupancy and other code conditions. ASTM E3158 is one standard test method for measuring the air leakage rate of a large or multi-zone building.
A fan-pressurization leakage test is different from a survey of building pressures under normal operation.
In Texas, the State Energy Conservation Office identifies the 2015 IECC, in effect since November 1, 2016, as Texas’s statewide commercial energy code. Actual project requirements depend on the locally adopted edition and amendments.
Keeping Ventilation Balanced and Verified
A tighter building still needs mechanical ventilation, with ventilation and pressure relationships verified at TAB and rechecked when use or equipment changes.
Frequently Asked Questions
Is stack effect good or bad?
Neither on its own. It drives natural ventilation in some designs, but in a mechanically conditioned commercial building, uncontrolled stack effect causes drafts, wasted energy, and pressure problems.
What is stack effect in HVAC?
It is the buoyancy-driven pressure the building adds to what the HVAC system produces. It shifts the airflow and pressure relationships the system was balanced to, and it changes with outdoor temperature.
How do you calculate the stack effect?
NRC Canada’s formula is ps = 0.52 x P x H x (1/To – 1/Ti), with H as total building height in feet and temperatures in degrees Rankine. See the worked examples above for the assumptions.
How do you reduce stack effect in a commercial building?
Use vestibules or revolving doors at entrances, tighten floor and shaft separations, and seal the envelope. Then verify outside air, exhaust, and relief against the design.
Does stack effect happen in Texas?
Yes, in both directions. Normal stack effect occurs when it is colder outside than inside, and a reverse tendency occurs when buildings are cooled below outdoor temperature. Actual airflow also depends on wind and mechanical systems.
Get Building Pressure Problems Measured
Stack effect is a building condition, not an equipment fault, and the HVAC side of it is measurable and correctable. If your building has entrance door, elevator door, or comfort problems that change with the weather, talk with our TAB teams in Dallas, Houston, and San Antonio about EAB’s total system balancing services. A documented pressure survey helps separate stack effect from balancing and controls problems.